Wire Size and Voltage Drop Calculator
Enter the load, voltage and distance. Get the voltage drop and an estimated minimum wire size, taking the larger of the ampacity size and the voltage drop size.
Quick answer
Voltage drop is 2 x K x amps x one-way feet divided by the wire's circular mils for single phase, with K of 12.9 for copper and 21.2 for aluminum. Size the wire for the larger of its ampacity and the size that keeps drop within 3%. A 40 A, 240 V circuit 75 feet away needs 8 AWG copper.
Estimated minimum size
8 AWG
- Current to size for
- 40 A
- Smallest size for ampacity
- 8 AWG
- Smallest size for voltage drop
- 8 AWG
- Voltage drop at this size
- 4.69 V (1.95%)
- Ampacity at this size (60 C column)
- 40 A
- Breaker limit for this size
- See code
A planning aid, not a code determination. Final conductor size must meet the electrical code adopted where the work is done, including temperature and bundling adjustments, terminal ratings, conduit fill and the type of load, and the installation must be done and inspected as the local authority requires. Have a licensed electrician confirm it.
Opens the free invoice maker with this as the first line. Add your rate and download the PDF.
Important limits of this calculator
This is a planning aid. It is not a code determination and it does not replace a licensed electrician, a permit or an inspection. Final conductor size must satisfy the electrical code adopted where the work is done, and that code decides what applies to your job.
- Ampacity here uses the 60 C column of NEC Table 310.16, the conservative column that applies to terminations on circuits of 100 A or less unless the equipment is listed for higher
- It does not apply temperature correction, adjustment for more than three current-carrying conductors, or conduit fill
- It does not size for motors, EV charging, solar, welders or other loads with their own code rules
- It stops at 4/0 AWG. Larger services and feeders need engineered sizing
- The 3% drop limit is a recommendation in the code, not a requirement, and local rules differ
The two sizes: ampacity and voltage drop
A conductor has to be large enough not to overheat, which is its ampacity, and large enough that the voltage at the far end stays close to the supply voltage, which is voltage drop. The ampacity size depends only on the current. The voltage drop size also depends on distance, so on a long run it is often the bigger of the two. The calculator shows both and uses the larger.
A worked example
A 40 A load at 240 V on a single-phase run of 75 feet. At 3% the allowed drop is 7.2 V. Circular mils needed are 2 x 12.9 x 40 x 75 divided by 7.2, which is 10,750. 10 AWG has 10,380 circular mils, which is just short, so the drop size is 8 AWG at 16,510. 8 AWG copper also carries 40 A in the 60 C column, so 8 AWG is the answer, with a drop of 4.69 V, or 1.95%.
Why the small sizes have a breaker limit
The code caps the breaker on the smallest conductors regardless of the table ampacity: 15 A on 14 AWG copper, 20 A on 12 AWG and 30 A on 10 AWG, with lower limits for aluminum. The calculator shows this limit when the result is one of those sizes, so a larger breaker is never paired with a small wire.
Wire Size Calculator questions
01How do I calculate voltage drop?
For single phase, multiply 2 by K by the load in amps by the one-way distance in feet, then divide by the conductor's circular mils. K is 12.9 for copper and 21.2 for aluminum. For three phase, use the square root of 3 in place of 2.
02What voltage drop is acceptable?
The electrical code recommends, as an informational note, no more than 3% on a branch circuit and 5% combined for feeder and branch. These are recommendations, not requirements, but they are the usual design targets.
03What size wire do I need for a 50 amp circuit?
It depends on distance, material and conditions. In the 60 C column, 6 AWG copper carries 55 A, so 6 AWG is the usual starting point for a 50 A circuit, and a long run may need larger for voltage drop. Confirm with the code and a licensed electrician.
04What is a continuous load?
A load expected to run for three hours or more, such as lighting or EV charging. The code sizes conductors for 125% of a continuous load, which the calculator applies when you choose Yes.
05Why does the calculator use the 60 C column?
Terminations on circuits of 100 A or less are generally limited to the 60 C column unless the equipment is listed for a higher rating. Using it is the conservative choice, so the result is never smaller than that column allows.
06Does it work for aluminum wire?
Yes. Aluminum has higher resistance, so it needs a larger size than copper for the same load and distance, and it is not listed below 12 AWG here. Aluminum terminations need compatible lugs and the right installation practice.
07Is distance one-way or round trip?
Enter the one-way distance from the panel to the load. The formula already doubles it for single phase because current travels out and back.
08Can I use this to wire a house or install a circuit?
Use it to plan and to price the job. The installation itself should follow the code that applies, be permitted and inspected where required, and be done or reviewed by a licensed electrician.
09What wire gauge do I need for 30 amps?
In the 60 C column, 10 AWG copper carries 30 A, so it is the usual starting point for a 30 A load. A long run can need a larger wire gauge to keep voltage drop in check, and aluminum needs a larger size. Confirm with the code and a licensed electrician.
Ready when you are
From wire size to a paid invoice
Send the electrical estimate for online approval, then invoice with the permit itemized and a payment link. Free for 14 days.