Free calculator

    HVAC Tonnage, BTU and CFM Calculator

    Enter the cooling load from a Manual J calculation and the equipment you propose. See the load in tons, how far the equipment is above or below it, and the airflow it needs.

    Quick answer

    One ton of cooling is 12,000 BTU per hour. Divide a Manual J cooling load by 12,000 to get tons, and multiply tons by about 400 for the airflow in CFM. A 30,000 BTU/h load is 2.5 tons, so a 3 ton unit is 20% over it. Do not size equipment from square footage.

    Equipment vs calculated load

    +20%

    Load in tons
    2.5
    Standard sizes around the load
    2.5 ton
    Proposed capacity
    36,000 BTU/h
    Airflow at proposed size
    1,200 CFM
    Airflow at the load
    1,000 CFM

    Enter the total cooling load from a Manual J calculation. A square-footage guess is not a load: published Manual J results range widely, and rules of thumb tend to oversize. ACCA Manual S limits how far equipment may exceed the load, so check it before you commit. One ton is 12,000 BTU/h by definition.

    Opens the free invoice maker with this as the first line. Add your rate and download the PDF.

    Why this does not guess from square feet

    Many calculators turn square footage into tons using a rule of thumb, often 400 to 600 square feet per ton. ACCA, the body behind Manual J, published a comparison of those rules with real load calculations. Across 40 Manual J results the range was 624 to 3,325 square feet per ton, with an average of 1,431, so the rule of thumb fits very few homes and usually points to oversized equipment. Load depends on insulation, windows, orientation, air leakage, ducts and climate, none of which square footage captures.

    So this tool starts from a real load and answers the questions a contractor actually has: what is that in tons, how far over the load is the equipment I am quoting, and how much airflow does it need.

    Why oversizing is a problem

    • An oversized air conditioner can cool the air quickly and shut off before it removes much moisture, leaving a damp, clammy house
    • It can start and stop often, which adds wear and can make temperatures swing
    • It can be louder and cost more to buy and to run
    • Ducts sized for the right equipment may be too small for the bigger unit

    A worked example

    A Manual J load of 30,000 BTU/h divided by 12,000 is 2.5 tons. Standard sizes are 2.5 and 3 tons, so a 3 ton unit is 36,000 BTU/h, or 20% above the load. At 400 CFM per ton, the 3 ton unit needs 1,200 CFM and the load alone needs 1,000. Whether 20% over is acceptable is governed by ACCA Manual S and the equipment's capacity at the design conditions, which this calculator does not decide.

    What to do instead of guessing

    Run a Manual J load calculation for the home, select equipment against it with Manual S, and design the ducts with Manual D. Many contractors use load calculation software for this. This calculator is for the arithmetic around that process, and for explaining the numbers to a customer.

    01

    How many BTU is one ton of cooling?

    One ton of cooling is 12,000 BTU per hour. The unit comes from the cooling effect of melting one ton of ice over 24 hours.

    02

    How do I convert BTU to tons?

    Divide the BTU per hour by 12,000. A 36,000 BTU/h system is 3 tons, and a 30,000 BTU/h load is 2.5 tons.

    03

    How many square feet does a ton of AC cool?

    There is no reliable figure. Rules of thumb say 400 to 600 square feet per ton, but ACCA's comparison of 40 Manual J results found 624 to 3,325 square feet per ton. The load depends on the home, so it needs a load calculation.

    04

    What is a Manual J load calculation?

    It is the ACCA method for calculating a home's heating and cooling loads from its construction, windows, orientation, air leakage, ducts, climate and occupants. It is the standard starting point for sizing equipment.

    05

    How much airflow does an AC need per ton?

    A common design figure is about 400 CFM per ton, and many systems are designed between 350 and 400. The right number depends on the equipment and the climate, so follow the manufacturer's data.

    06

    Is a bigger air conditioner better?

    Usually not. An oversized unit can cool too quickly to remove humidity, cycle on and off often and cost more. Equipment should be selected against the calculated load, within the limits of ACCA Manual S.

    07

    How much can equipment exceed the load?

    ACCA Manual S sets limits for how far selected equipment may exceed the calculated load, and the limits depend on the equipment type. Check the current edition rather than relying on a single percentage.

    08

    Can I put the result on an invoice?

    Yes. Use Add to an invoice to open the free invoice maker with a Manual J line and the installation as lines. Enter your rates and download the PDF.

    09

    Is this an HVAC load calculator?

    No. An HVAC load calculator, in the Manual J sense, works out the load from the building's construction, windows, air leakage and climate. This tool takes that result and converts it to tons, checks oversizing and gives airflow.

    10

    What AC size do I need?

    The right AC size comes from a Manual J load calculation, not from square footage alone. Once you have the load, divide it by 12,000 for tons and choose equipment close to it, within the limits of ACCA Manual S.